Publication 2093-UM001A-EN-P — March 2007

Configure and Startup the Kinetix 2000 Drive System

105

5. Repeat steps 3 and 4 for each axis module.

Node Addressing Example 1

In Example 1, the Kinetix 2000 (seven-axis) system 1 power rail contains one
IAM, four AMs, a shunt, and one slot filler module. In this example, the shunt
module and slot filler do not use the node addresses, although having a slot
assignment. The node address can be reserved by not assigning it, and this will
provide for future expansion of the system.

1 2 3

1 2 3

ON

OFF

DIP Switches Set For

4M Baud Application

Low Power Setting

DIP Switches Set For
8M Baud Application
High Power Setting

Switch in OFF position

Switch in ON position

Integrated Axis Module,

(2093-AC05-MP

x)

SERCOS Baud Rate

and Optical Power Switches

SERCOS interface

TM

Tx (rear)

Rx (front)

OK

CP

1 2 3

1 2

ControlLogix Chassis

1756-M08SE SERCOS
Interface Module

Kinetix 2000
System 2
(2093-PRS2 power rail)

SERCOS Fiber-optic Ring

Receive

Transmit

Receive

Transmit

Transmit

Receive

Kinetix 2000

System 1

(2093-PRS7 power rail)

Node Addresses:
18 = axis 1 (single-wide AM)
17 = axis 0 (IAM)

Node Addresses:
* = Slot Filler (not an axis)
* = Shunt (not an axis)
14 = axis 4 (single-wide AM)
13 = axis 3 (single-wide AM)
12 = axis 2 (single-wide AM)
11 = axis 1 (single-wide AM)
10 = axis 0 (IAM)
* Reserved for expansion.