Publication 2093-UM001A-EN-P — January 2007

98

Connecting the Kinetix 2000 Drive System

Shunt Module Connections

Follow these guidelines when wiring your shunt.

Shunt Module Wiring

Shunt Module Jumper Settings

(1)

These jumpers are factory installed.

With this shunt module

Cat. No.

Do this

Power rail mounted shunt
module.

2093-ASP06

• Verify the internal shunt jumper is in place between RC-2 and RC-3, as shown in the figure below.
• Verify the thermal switch jumper is in place between TS-1 and TS-2, as shown in the figure below.

32

1

21

DC+

INT
COL

TS1

TS2

Shunt Module, Front View
(2093-ASP06)

Jumpers

DC+

INT

COL

TS1

TS2

32

1

21

External Shunt Resistor

(RC) Connector

Shunt Module, Front View

(2093-ASP06)

External Thermal Switch

(TS) Connector