Mount the modules – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual

Page 40

Advertising
background image

Publication 2093-UM001A-EN-P — March 2007

40

Mounting the Kinetix 2000 Drive System

Mount the Modules

Follow these steps to mount the IAM, AM, SM, and SF modules. All modules
mount to the power rail using the same technique.

1. Determine the next available slot and module for mounting.

2. Insert the module in the power rail slot.

a. Align the module locking screw with its corresponding slot on the

power rail.

b. Push the module straight forward, by applying force at the top and

bottom of the front cover.

IMPORTANT

Invalid module positioning on a 2093-PRS8S power rail may result in
incorrect operation.

IMPORTANT

The IAM must be positioned in the leftmost slot of the power
rail. Position your axis modules, shunt module, and slot fillers to
the right of the IAM.

ATTENTION

To avoid damage to the pins located on the back of each module
(IAM, AM, SM, and SF) and to make sure that module pins mate
properly with the power rail, install modules as shown below.

The power rail must be mounted with the connectors in an
upright or vertical orientation to the panel. This provides proper
cooling of the modules. Do not mount modules if the power rail
is not within three degrees of vertical.