Publication 2093-UM001A-EN-P — March 2007

158

Specifications and Dimensions

Circuit Protection under NEC 1999 110-10 (allowed but no longer preferred)

Use class CC, J, L, or R fuses, with current rating as indicated in the table
below. The following fuse examples and Allen-Bradley circuit breakers are
recommended for use with integrated axis modules (2093-AC05-MPx) when
the Line Interface Module (LIM) is not used.

Main and Control Input Power Fuse Specifications

Required Protection

under 110-10 of

NEC 1999

Allowed But

No Longer Preferred

Distribution

Blocks

Traditional
Current Limit
Fused
Disconnect or
Breaker
Rated for
Short Circuit
Available
Limiting to
Short Circuit
Rating of Down
Stream Breaker

Breakers Selected

for Device Protection

With Limited Short

Circuit Interrupt

Capability

Drive

Drive

Drive

Required Protection

under 110-10 of

NEC 1999

Allowed But

No Longer Preferred

Traditional
Current Limit
Fused
Disconnect or
Breaker
Rated for
Short Circuit
Available
Limiting to
Short Circuit
Rating of Down
Stream Breaker

Breakers Selected

for Device Protection

With Limited Short

Circuit Interrupt

Capability

Distribution

Blocks

IMPORTANT

Line interface modules (2094-ALxxS and 2094-XL75S-Cx) provide
branch circuit protection to the IAM.

Line interface module 2094-AL09 contains a supplementary protection
device, 1492-CB (UL 508), and therefore class CC or J fuses with 5kA
SCCR must be used on the line side.

Follow all applicable NEC and local codes.

Catalog Number

Main Input Power

Control Input Power

Main Input

Fuse

Circuit Breaker
1492 Series

(1)

Circuit Breaker
140M Series

(1)

Fuse

(2)

Circuit Breaker 1492
Series

(1)

2093-AC05-MP1

170...264V ac
three-phase

KTK-R-20 (20A)

1492-CB3H300

140M-F8E-C16

FNQ-R-10 (10A)
or
KTK-R-5 (5A)

1492-CB2H060

2093-AC05-MP2

2093-AC05-MP5

2093-AC05-MP1

170...264V ac
single-phase

N/A

2093-AC05-MP2

2093-AC05-MP5

(1)

When using Bulletin 1492 or 140M circuit protection devices, the maximum short circuit current available from the source is limited to 5000 A.

(2)

Fuse selection for control power is appropriate for an eight-axis system with the specified IAM.

ATTENTION

Bulletin 1492 and 140M circuit breakers should not be used on the
output of an ac drive as an isolating disconnect switch or motor
overload device. These devices are designed to operate on sine wave
voltage and the drive’s PWM waveform does not permit proper
operation. As a result, damage will occur to the device.