C - upgrading firmware, Introduction, Before you begin – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual

Page 187: Appendix c, Upgrading firmware, Introduction before you begin, Appendix

Advertising
background image

187

Publication 2093-UM001A-EN-P — March 2007

Appendix

C

Upgrading Firmware

Introduction

This appendix provides procedures for upgrading firmware. The procedure
requires you to complete two steps:

• Use Drive Explorer or Drive Executive to setup the Kinetix 2000 axes

to be flashed.

• Use Hyperterminal to flash the firmware in the selected drives.

Before You Begin

Obtain the following software and information before you begin.

Topic

Page

Before You Begin

187

Selecting Software Tools to Upgrade the Kinetix 2000 Drive Firmware

188

Using Drive Explorer to Setup the Kinetix 2000 Drives to Flash

188

Using Drive Executive to Setup the Kinetix 2000 Drives to Flash

188

Using Hyperterminal to FLASH the Kinetix 2000 Drive

202

Description

Catalog Number

Firmware Revision

DriveExplorer software

9306-4EXP02ENE

5.02 or later

Drive Executive software

v4.01 or later

RSLinx

(1)

(1)

RSLinx is required by Drive Executive software, but it is not required by DriveExplorer software.

2.50.00 or later

Firmware Upgrade file for your Kinetix 2000 IAM/AM

(2)

(2)

The correct MSI ControlFlash for Hyperterminal use is a binary file ending in _a. If unable to locate the file,
contact technical support at 440-646-5800 to receive the file email.

Anacanda Serial to DPI Adapter

(3)

(3)

The Serial to DPI Adapter, catalog number 1203-SSS (Series B), contains: 1203-SFC cable from PC serial to
Anacanda, 1202-Cxx cable from Anacanda to DPI port, and an Anacanda body.

1203-SSS (Series B)

3.004 or later

Personal computer with Hyperterminal software

IMPORTANT

Control power (230V ac, single phase) must be present at CPD-1 and
CPD-2 prior to flashing your drive.

The seven-segment Fault Status display on the IAM (inverter) or AM
to upgrade must display a fixed 2, 3, or 4 before beginning this
procedure. This indicates the IAM/AM is recognized on the SERCOS
ring.