Planning the Kinetix 2000 Drive System Installation

Multiple Subpanels and Cabinet Recommendations

Establishing Noise Zones

Observe the following guidelines when a LIM (2094-AL09) is used in the
Kinetix 2000 system and mounted left of the IAM:

This layout is preferred due to the reduced size of the very dirty zone.

• The clean zone (C) is to the right and beneath the Kinetix 2000 system

(grey wireway).

• The dirty zone (D) is to the left and above the Kinetix 2000 system, and

above and below the LIM (black wireway).

• The very dirty zone (VD) is limited to where the LIM VAC output

jumpers over to the IAM. Shielded cable is required only if the very dirty
cables enter a wireway.

• The SERCOS fiber-optic cables are immune to electrical noise.

Bond the top and bottom of each subpanel to the cabinet using
25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid.

Scrape the paint around each fastener to
maximize metal to metal contact.

Cabinet ground bus

bonded to the subpanel.