Ungrounded three-phase power configurations, Important, Attention – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual

Page 65

Advertising
background image

Publication 2093-UM001A-EN-P — January 2007

Connecting the Kinetix 2000 Drive System

65

Ungrounded Three-phase Power Configurations

Ungrounded power configurations are allowed, but you must jumper across a
resistor (internal to the IAM) to prevent high electrostatic build-up. The
ungrounded power configuration (shown below) does not provide a neutral
ground point. The IAM has a ground jumper set for grounded power
distribution (default configuration).

Ungrounded Three-phase Power Configuration (delta secondary)

IMPORTANT

If you determine that you have ungrounded power distribution in your
facility, you need to move the default jumper (configured for grounded
power) to the ungrounded power position to prevent electrostatic
buildup inside the IAM.

Refer to the Setting the Ground Jumper in Ungrounded Power
Configurations
on page 69 for more information.

ATTENTION

Ungrounded systems do not reference each phase potential to a
power distribution ground. This can result in an unknown potential to
earth ground.

L1

L2

L3

Integrated Axis Module, Front View

(2093-AC

xx

-MP

x

)

Conduit/4-Wire Cable

3-Phase

Input VAC

Ground

To Power Rail Ground Stud

Bonded Cabinet

Ground

Transformer

Internal Jumper Must Be Changed

For This Configuration