Planning the Kinetix 2000 Drive System Installation

31

Observe the following guidelines when a LIM (2094-AL09) is used in the
Kinetix 2000 system and mounted above the IAM:

• The clean zone (C) is to the right and beneath the Kinetix 2000 system

(grey wireway).

• The dirty zone (D) is to the left and above the Kinetix 2000 system, and

above and below the LIM (black wireway).

• The LIM VAC output is very dirty (VD). Use shielded cable with a braid

clamp attached at both ends of the cable to reduce the rating to dirty
(D).

• The SERCOS fiber-optic cables are immune to electrical noise.

Establishing Noise Zones (LIM mounted above IAM)

(1)

For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference
Manual, publication GMC-RM001.

(2)

If IAM/AM I/O cable contains (dirty) relay wires, route cable in dirty wireway.

(3)

When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For
examples, refer to Chapter 4 of the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001.

D

D

C

C

VD

Dirty Wireway

Line Interface Module

Kinetix 2000
Drives

Clean Wireway

Power Cables

Very Dirty LIM/IAM
connections must be
shielded with braid
clamp at both ends.

Route Encoder/Analog/Registration

Shielded Cables

Fiber-optic Cable

Route Motor Power and
24V dc I/O Shielded Cables

(1)

I/O and Feedback Cables

(2)

No Sensitive

Equipment

Within 150 mm

(3)

V ac LINE

V ac LOAD