Publication 2093-UM001A-EN-P — March 2007

204

Upgrading Firmware

You may notice that the baud rate is the same setting as used with Drive
Explorer or Drive Executive and is tied to the baud rate of the 1203-SSS
device.

8. Select OK.

This completes the configuration of your Hyperterminal session.

Flashing Kinetix 2000 Firmware with Hyperterminal

This procedure assumes you have identified which axis modules require
flashing, have set the Axes to Flash parameters, and have configured a
Hyperterminal session.

1. Press Enter to open the Hyperterminal main menu.

If you have difficulty opening a Hypterminal session, verify you have:

• the port setting the same as in the previous section.
• the 1203-SSS connected.
• the baud rate setting the same as in the previous section.

IMPORTANT

You must also know where to find your firmware update
(extension _a or binary) file.