Part 3 Positioner Mode

Chapter 5 T

eaching Mode

335

Part 3 Positioner Mode

5.2

Home Return

In the teaching mode, no dedicated home-return input is available.

Home return will be performed when the start signal is input after specifying a desired position in a

condition where home return is not yet completed.

Timings associated with home-return operation are illustrated below.

Timing Chart of Home-return Operation (Teaching Positioner Mode)

Perform home-return operation by following the procedure explained below.

*

Before commencing the procedure, confirm that the ready output signal is ON, alarm output signal is

OFF, and home-return complete output signal is OFF.

[1] Turn ON the servo ON input signal.

[2] Confirm that the servo-ON status output signal is

ON.

[3]

Turn ON the start input signal.

[4] Confirm that the positioning complete output signal is

OFF.

[5]

Turn OFF the start input signal.

[6] Confirm that the home-return complete output signal

is ON. Home return is now completed.

* Pause input is a contact-B input signal (always ON), so keep this signal ON while home return is in

progress.

To operate the actuator using the start input, the servo ON input signal must be ON. If the servo ON input

signal is OFF, this operation command will not be accepted. Note, however, that only the command will be

ignored and no error will generate.

With the 2-axis specification, the controller has been configured at the factory so that the two axes will start home

return simultaneously.

You can cause either axis to start home return earlier than the other axis by changing the applicable parameter setting.

Specifically, change the setting in axis-specific parameter No. 13, “SIO/PIO home-return order” so that the parameter

value for the axis number corresponding to the axis for which you want to complete home return first, will become

smaller than the parameter value for the other axis number.

Example)

Cause axis 1 to perform home return after axis 2 has completed home return, set “1” for axis 1 and “0” for

axis 2 in axis-specific parameter No. 13.

Input

Output

Start

Servo ON

Alarm

Ready

Positioning complete

Home return complete

Servo ON status

Home return in progress

Warning : Turning the servo ON near the mechanical end may disturb the magnetic pole phase

detection, and may cause the magnetic pole unconfirmed error or the magnetic pole

detection error.

Put the slider or rod away from the mechanical end when turning the servo ON.