Chapter 4 Operationg

Part 1 Installation

58

Program 1

Program 2

T1: Duration after the ready output turns ON until

input of external start signal is permitted

T1 = 10 msec min.

T2: Duration after the program number is input

until input of external start signal is permitted

T2 = 50 msec min.

T3: Input duration of external start signal

T3 = 100 msec min.

T1: Time after the ready output turns ON until the

auto-start program start signal can be input to

input port No. *

T1 = 10 msec min.

* Auto program start:

Set “0” in other parameter No. 7, “Auto program

start setting.”

T1: T1: Time after the ready output turns ON until

input function specification value 3 (soft reset

signal) can be input to input port No. *

T1 = 10 msec min.

T2: T2: Time until the soft reset signal becomes

effective

T2 = 1 sec min.

T3: Time after the soft reset signal is cancelled

until the ready signal is output

T1: Time after the ready output turns ON until input

function specification value 4 (servo ON signal)

can be input to input port No. *

T1 = 10 msec min.

T2: Interval after the servo is turned OFF until it is

turned ON again

T2 = 1.5 sec min.

T1: Time after the emergency stop input is reset until

the drive-source cutoff reset signal can be input.

T1 = 2 sec min.

T2: Time during which the drive-source cutoff reset

signal is input

T1 = 10 msec min.

T3: Time during which the pause reset signal is input

T1 = 10 msec min.

Warning : Turning the servo ON near the mechanical end may disturb the magnetic pole phase detection,

and may cause the magnetic pole unconfirmed error or the magnetic pole detection error.

Put the slider or rod away from the mechanical end when turning the servo ON.

Part 1 Installation

Ready output

Program number

input

External start

input

Ready output

Auto-start program

start signal input

Auto program

start

Ready output

Soft reset signal

input

Program starting

Ready output

Servo ON signal

input

Servo ON

Program starting

Emergency stop

Drive-source

cutoff reset

Pause reset

[2] Timing chart

[1] Program start

[2] Auto program start

* Set input function specification value 5 (auto-start program start signal) for input port No. *.

[3] Soft reset signal

* Set input function specification value 3 (soft reset signal) for input port No. *.

[4] Servo ON signal

* Set input function specification value 4 (servo ON signal) for input port No. *.

[5] When the recovery type after emergency stop or enable operation is set to “Operation continued”

* Set other parameter No. 10 to “2,” and set input function specification value 7 (operation-pause reset signal) for input port

No. *. Set input function specification value 17 (drive-source cutoff reset input signal) for other input port No. *.