IAI America ASEL User Manual

Page 365

Advertising
background image

Part 3 Positioner Mode

Chapter 6 DS-S-C Compatible Mode

343

Part 3 Positioner Mode

5.2

Home Return

In the DS-S-C1 compatible mode, no dedicated home-return input is available.

Home return will be performed when the start signal is input after specifying position No. 0. The

positioning complete output signal is OFF after the power is input when home return is not yet completed.

Timings associated with home-return operation are illustrated below.

T1: Time after the ready output signal turns ON until input of the start signal becomes

possible (50 msec or more)

T2: Start signal input (50 msec or more)

Timing Chart of Home-return Operation (Positioner Mode)

Perform home-return operation by following the procedure explained below.

* Before commencing the procedure, confirm that the ready output signal and alarm output signal are ON.

[1] Specify position No. 0 (PC1 through 1000 are all OFF).

[2] Turn ON the start input signal. (The signal should remain ON continuously for 30 msec or more (T2).)

[3] Turn OFF the start input signal.

[4] Confirm that the positioning complete output signal is ON. Home return is now completed.

With the 2-axis specification, the controller has been configured at the factory so that the two axes will

start home return simultaneously.

You can cause either axis to start home return earlier than the other axis by changing the applicable

parameter setting.

Specifically, change the setting in axis-specific parameter No. 13, “SIO/PIO home-return order” so that the

parameter value for the axis number corresponding to the axis for which you want to complete home

return first, will become smaller than the parameter value for the other axis number.

Example)

Cause axis 1 to perform home return after axis 2 has completed home return, set “1” for axis

1 and “0” for axis 2 in axis-specific parameter No. 13.

Start

Alarm

Ready

Positioning complete

Input

Output

Home Return

Stop

Warning : Turning the servo ON near the mechanical end may disturb the magnetic pole phase

detection, and may cause the magnetic pole unconfirmed error or the magnetic pole

detection error.

Put the slider or rod away from the mechanical end when turning the servo ON.