Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-43

154

Stop Dwell Time
Sets an adjustable delay time between detecting zero speed
and disabling the speed and torque regulators, when
responding to a stop command.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Sec
0
0
10
Linkable, Read-Write, Floating Point
Dynamic Control
Stop/Brake Modes

Drive Operation when paramter 154 [Stop Dwell Time] equals zero

Drive Operation when paramter 154 [Stop Dwell Time] is greater than zero

No.

Name
Description

Values

IMPORTANT

Consult industry and local codes when setting the value of this parameter.

P 160 [Zero Speed Lim]

Speed

Dr

iv

e Receiv

es Stop Command

0

Time

Dr

iv

e Detects Zero Speed

and

Tu

rns Off Regulators

When parameter 154 [Stop Dwell Time] equals
zero, the drive turns off the velocity and torque
regulators when it detects zero speed.

P 160 [Zero Speed Lim]

Speed

Dr

iv

e Receiv

es Stop Command

0

Time

Dr

iv

e Detects Zero Speed

Dr

iv

e

Tu

rns Off Regulators

P 154 [Stop Dwell Time]

When parameter 154 [Stop Dwell
Time] is greater than zero, the drive
delays turning off the velocity and
torque regulators for the amount of
time specified by parameter 154.