Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 285

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

1756-DMF30 Specific Information C-33

330

Fault TP Data
Displays the data selected by parameter 329 [Fault TP Sel].

Default:
Min:
Max:
Type:
File:
Group:

0
-2200000000
2200000000
Non-Linkable, Read-Only, Floating Point
Utility
Test Points

369

SL CommLoss Cnfg
Enter a value to determine what is done with the data received
from SynchLink when a communication loss occurs.

• Value 0 - Ignore configures the drive to continue

running, as normal, when this event occurs

• Value 1 - Alarm configures the drive to continue

running and set the appropriate alarm bit when this
event occurs

• Value 2 - FltCoastStop configures the drive to perform a

coast stop and set the appropriate fault bit, in response
this event.

• Value 3 - Flt RampStop configures the drive to perform

a ramp stop and set the appropriate fault bit, in
response this event.

• Value 4 - FltCurLimStp configures the drive to perform a

current-limit stop and set the appropriate fault bit, in
response this event.

Default:

Val 2

FltCoastStop

Options:

Val 0
Val 1
Val 2

Ignore
Alarm
FltCoastStop

File:
Group:

Utility
Fault/Alm Config

370

SL CommLoss Data
Enter a value to configures the drive's response to SynchLink
communication loss. Refer to parameter 1229 [SL Error Status]
for possible causes of communication loss.

• Value 0 - Zero Data Resets data to zero

• Value 1 - Last State Holds data in its last state

Default:

Val 1

Last State

Options:

Val 0
Val 1

Zero Data
Last State

File:
Group:

Utility
Fault/Alm Config

No.

Name
Description

Values

ATTENTION

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 369 [SL
CommLoss Cnfg] lets you determine the action of the drive if communications
are disrupted. By default this parameter causes the drive fault and coast to a stop.
You can set this parameter so that the drive continues to run. Precautions should
be taken to ensure that the setting of this parameter does not create hazards of
injury or equipment damage.

ATTENTION

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 370 [SL
CommLoss Data] lets you determine the action of the drive if communications
are disrupted. By default this parameter causes the drive module to hold the data
in its last state. You can set this parameter so that the drive resets the data to zero.
Precautions should be taken to ensure that the setting of this parameter does not
create hazards of injury or equipment damage.