Publication 1756-UM522B-EN-P - February 2003

B-168 1756-DMD30 Specific Information

5

ID TestAbort

The drive has failed an armature identification test, field
identification test or resolver balance calibration test.

6

Fld OvrCurr

Field current has exceeded 150% of the value in parameter
2185 [Hot Field Curr].

7

Arm Fdbk Rev

Armature feedback wiring is reversed - the polarity of the
feedback is the oposite of expected.

8

CT Fdbk Rev

Current transformer feedback is reversed - the polarity of
the feedback is the oposite of expected.

12

PMI Fan Loss

Airflow through the PMI rack is not being sensed. A
solid-state airflow switch in the PMI power supply monitors
airflow.

13

Rail IO Comm

A rail communication warning event has occurred.
Parameter 2044 [Rail Port 0 Faul] and parameter 2050 [Rail
Port 0 Faul] enumerate these faults.

14

PMI CommSync

The PMI Processor and the Drive Module are momentarily
not synchronized.

15

PMI Comm

A fiber-optic communication error has been detected
between the PMI Processor module and the Drive Module.
Communication errors in two consecutive messages will
cause a fault.

Bit

Fault Name

Fault Description

Advertising