Publication 1756-UM522B-EN-P - February 2003

1756-DMF30 Specific Information C-93

2200

PMI Drive Config
Set bits to configure the PMI processor.

• Bits 0-7 [PMI OS Sel] indicate the catalog number of

the Drive Module (do not modify these settings).

• Bit 8 [Arm Reg Used] enables control of the motor

armature.

• Bit 9 [re Bdge Usd] enables control of a regenerative

armature bridge.

• Bit 10 [S12 Config] enables twelve-pulse control.

• Bit 11 [M-Cont Used] enables Drive Module control of

the main contactor.

• Bit 12 [Fld Reg Used] enables control of the motor field.

• Bit 13 [4 quad fld] enables four-quadrant control of the

motor field.

• Bit 14 [3ph fld gene] is not used.

Default:

0000 0000 0000 0001

Options

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
PMI OS Sel
Arm Reg Used
Rev Bdge Usd
S12 Config
Reserved
Fld Reg Used
4 quad fld
3ph fld gene
Reserved

File:
Group:

DPS/PMI
Drive Config

2201

PMI I/O Config
Set bits to configure the rail I/O and speed feedback in the PMI
processor.

• Bits 0-3 [Prt 0 Config] form a nibble that configures the

port 0 rail I/O

• Bits 4-7 [Prt 1 Config] form a nibble that configures the

port 1 rail I/O: 0 = no I/O, 1 = Digital I/O, 2 = 2 Channel
Analog Input / 2 Channel Analog Output, 3 = 4 Channel
Analog Output, 4 = 4 Channel Analog Input.

• Bits 8-11 [Res Type] form a nibble that configures the

resolver type: 0 = no resolver, 1 = 1 x resolver, 2 = 2 x
resolver, 3 = 5 x resolver.

• Bits 12-15 [SpdFdbk Type] form a nibble that configures

the speed feedback type: 0 = no speed feedback, 1 =
tachometer, 2 = resolver.

Default:

0000 0000 0000 0000

Options

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Prt 0 Config
Prt 0 Config
Prt 0 Config
Prt 0 Config
Prt 1 Config
Prt 1 Config
Prt 1 Config
Prt 1 Config
Res Type
Res Type
Res Type
Res Type
SpdFdbk Type
SpdFdbk Type
SpdFdbk Type
SpdFdbk Type

File:
Group:

DPS/PMI
Drive Config

2202

AC LineVolt(RMS)
Enter the nominal input voltage to the Armature Power
Module. The PMI processor uses this value to determine the
threshold (15% below this value) for indicating the low AC line
voltage warning.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Volt
230
10
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

2203

Out Volt Rating
Enter the maximum output voltage the Power Module will
produce.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Volt
10
10
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

No.