Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 40

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

4-4

Installing the Drive Module

Figure 4.1 SynchLink Connections

Refer to See Table 1.B on page 1-3 for information on available
pre-configured fiber optic SynchLink cables.

Table 4.A lists the possible connections that might be made to your
1756-DM module and where to connect the fiber optic cable.

Table 4.A
Making Fiber Optic Cable Connections to the 1756-DM Module

If your 1756-DM module
is configured to:

Make this fiber optic cable connection:

transmit data only

Connect the fiber optic cable to the rear port. The other end
of the cable should be connected to a device receiving data
over the SynchLink from your 1756-DM module.

receive data only

Connect the fiber optic cable to the front port. The other end
of the cable should be connected to a device transmitting
data to your 1756-DM module over the SynchLink.

transmit and receive data

1. Connect the fiber optic cable going to (i.e. transmitting

the data to) a module receiving the data to the front port.

2. Connect the fiber optic cable coming from (i.e. receiving

the data from) a module transmitting data to the rear port.

Tx Rx

Tx (rear)

Rx (front)

Advertising