Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 362

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

C-110 1756-DMF30 Specific Information

8

Bad FML Req

More than one incompatible Field operating mode is
requested at a time in parameter 166 [Motor Ctrl
Cmmd]. The following operating modes are mutually
exclusive:

•••• Field Alpha Test

•••• Field Identification Test

•••• Field Run

This bit is also set if you have attempted to restart the
drive without resetting the appropriate command bits
from parameter 166. Note that the bits in register 166
are edge-sensitive.

9

F Par NotLod

Field configuration parameters have not been
downloaded into the PMI module from the Dive
Module.

10

F Gns NotLod

Field configuration parameters have not been
downloaded into the PMI module from the Dive
Module.

11

F Flt Rst Rq

Previous field faults (parameter 2122 [MC Faults]),
e.g., field loss and line synchronization loss faults,
have not been cleared.

14

F FB or CFG

A field current feedback fault or configuration error
has occured:

•••• The drive has sensed field current feedback

when the field is off.

•••• You have attempted to turn on the field without

setting parameter 2200 [PMI Drive Config] bit
12 [Fld Reg Used].

Bit

Fault Name

Fault Description