Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 346

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

C-94 1756-DMF30 Specific Information

2204

Out Curr Rating
Enter the Power Modules 100% output DC Amp rating.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Amps
1
1
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

2205

Curr Xfmr Ratio
Defines the input to output ratio of the current transformer in
the Power Module. This value can be found on the Power
Module's nameplate.

Default:
Min:
Max:
Type:
File:
Group:

1
1
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

2206

Field AC ln Volt
Enter the nominal voltage at the Field Power Module input. If
an isolation transformer is used, enter the secondary voltage.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Volt
1
1
32767
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

2207

Fld OutCurrRatng
Enter the Field Power Module's DC Amps output rating. This
value can be found on the Power Module's nameplate.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Amps
15
1
327.67
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

2208

Anlg Tach Volts
Enter the tachometer voltage that will be present when the
motor is turning at the speed specified in parameter
2181[Overspd Trip Pt].

Units:
Default:
Min:
Max:
Type:
File:
Group:

Volt
5
5
327.67
Non-Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Drive Config

No.

Name
Description

Values

Advertising