Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 70

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

6-2

Troubleshooting the Drive Module

Use the table on the next page to troubleshoot your module.

LED Indicator Display

Means

Take this Action

OK

Green

Connection is running.

None

Flashing
Green

Inhibited I/O connection.

None

Red

Non-Recoverable Fault

Remove module from
service

Flashing Red

Flash download in progress.

None

Off

Module is powered down.

None

DRIVE
FAULT

Red

Module is faulted.

See Fault Status
parameters.

Off

No fault is present or module is
powered down.

None

LINK
SYNC

Green

The module is the time master or a
time relay and synchronization is
complete.

None

Flashing
Green

The module is configured as a time
relay from CST to SynchLink but is not
synchronized with a CST master on
the backplane.

N/A

The module is configured as a time
relay from SynchLink to CST but has
not synchronized with the upstream
device.

N/A

Flashing Red

The module is configured as a CST
master and has detected another CST
master.

N/A

The module is configured as a time
master on SynchLink and has
received time information from another
time master on SynchLink.

Ensure that only 1 time
master is present and
transmitting time
information on SynchLink.

Off

The module is not configured as a
time master or time relay or module is
powered down.

None

OS OK

Green

System and parameter constants
loaded.

None

Off

Checksum failure.

Reflash the module.

DRIVE
COMM
OK

Green

DPS communication is active and
synchronized.

None

Off

DPS communication is not active, is
not synchronized, or the module is
powered down.

Verify that cables are
securely connected.

LINK
COMM

Green

The module is configured and
receiving valid data from SynchLink.

None

The module is configured and enabled
to only transmit on SynchLink.

None

Off

The module is configured but not
receiving valid data from SynchLink.

Verify that cables are
securely connected.

The module is configured but not
enabled to transmit on SynchLink.

Enable module transmitter.

Module is powered down.

Power the module.

Advertising