Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-51

169

Drive I/O Status
Indicates status of PMI functions.

Default:

0000 0000 0000 0000

Options:

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Run Perm
M-Cont Fdbk
Aux In 2
Aux In 3
Aux In 4
Aux In 5
Res Gain OK
Res Bal OK
StrobeDetect
Strobe Level
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

File:
Group:

Utility
Diagnostics

171

Set Speed Lim
Creates a tolerance - hysteresis band around the value in
parameter 41 [Limited Spd Ref] for comparison to average
speed feedback. The comparison controls bit 14 [At Setpt Spd]
of parameter 155 [Logic Status]. In general bit 14 [At Setpt
Spd] turns on when the feedback is within the tolerance of the
reference. Technically - Turn-on level for rising feedback =
Limited Spd Ref - Limit. Turn-off level for rising feedback =
Limited Spd Ref + 2(Limit). Turn-on level for falling feedback =
Limited Spd Ref + Limit. Turn-off level for falling feedback =
Limited Spd Ref - 2(Limit).

Units:
Default:
Min:
Max:
Type:
File:
Group:

RPM
17.5
0
875
Linkable, Read-Write, Floating Point
Speed Control
Setpoint Monitor

No.

Name
Description

Values