Parameter 2122 [mc faults – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 358

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

C-106 1756-DMF30 Specific Information

Parameter 2122 [MC Faults]

This parameter indicates the occurance of a motor-control fault.
These bits are set when a fault event is detected. They stay latched
until bit 19 [Clear Fault] of parameter 152 [Applied Logic Cmd] or bit
19 [Clr Drv Wrn] of parameter 166 [Motor Ctrl Cmd] is set. If the fault
event remains present, the identifying bit is set again.

Bit

Fault Name

Fault Description

0

SCR Fault

An SCR has shorted. Check Parameter 2124 [Pwr
DeviceStatus] to determine which SCR has shorted.

3

AC Line Sync

AC line voltage has been missing for more than 2
seconds. Refer to parameter 2123 bit 3
[LineSyncLoss].

4

InstOvr Curr

Armature current feedback has exceeded 175% of the
value in parameter 2184 [PMI Curr Lim].

6

Field Loss

A field loss has been detected:

•••• Parameter 2132 [Fld Amps Fdbk] has been less

than parameter 2187 [FldLos Trip Pt] for more
than 5 times the electrical time constant of the
field. This assumes parameter 152 [Applied
LogicCmd] bit 30 [Field En] is on.

•••• Parameter 2132 [Fld Amps Fdbk] has been less

than parameter 2187 [FldLos Trip Pt] for more
than 30mS after the field has been turned on. -

•••• Parameter 2132 [Fld Amps Fdbk] has been

greater than 150% of parameter 2185 [Hot Fld
Cur] for more than 30mS.

•••• Parameter 2132 [Fld Amps Fdbk] has been

greater than parameter 2207 [Fld PMI Rating]
for more than 30mS.

8

TachWire Opn

A sine or cosine signal being used for speed or other
application feedback is missing, due to one of the
following causes:

•••• a resolver wiring connection has broken

•••• The value in parameter 2161 [Resolver Gain] is

too low.

The Drive Module always performs this test if
resolver feedback is selected (parameter 222 [Motor
Fdbk Sel] equals “0 - Resolver”), and when parameter
168 [Drive I/O Ctrl] bit 10 [Dis Brkn Wire] equals one.

9

ResolverCard

A fuse on the Resolver & Drive l/O module has blown.

11

PwrTech Card

The watchdog timer on the D-C Power Technology
module has expired. This fault disables the gate firing
circuitry.

Advertising