Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 155

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-75

371

Mtr OL Trip Cnfg
Enter a value to configure the drive's response to a “Motor
Overload Trip” exception event.

• Value 0 - Ignore configures the drive module to

continue running as normal, in response to this event

• Value 1 - Alarm configures the drive module to set the

appropriate alarm bit in response to this event

• Value 2 - FltCoastStop configures the drive module to

perform a coast stop and set the appropriate fault bit in
response to this event

• Value 3 - FltRampStop configures the drive module to

perform a ramp stop and set the appropriate fault bit in
response to this event

• Value 4 - CurLimStp configures the drive module to

perform a current limit stop and set the appropriate
fault bit in response to this event

Default

Val 2

FltCoastStop

Options:

Val 0
Val 1
Val 2
Val 3
Val 4

Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp

File:
Group:

Utility
Fault/Alm Config

372

Mtr OL Pend Cnfg
Enter a value to configure the drive's response to a “Motor
Overload Pending” exception event.

• Value 0 - Ignore configures the drive module to

continue running as normal, in response to this event

• Value 1 - Alarm configures the drive module to set the

appropriate alarm bit in response to this event

• Value 2 - FltCoastStop configures the drive module to

perform a coast stop and set the appropriate fault bit in
response to this event

• Value 3 - FltRampStop configures the drive module to

perform a ramp stop and set the appropriate fault bit in
response to this event

• Value 4 - CurLimStp configures the drive module to

perform a current limit stop and set the appropriate
fault bit in response to this event

Default

Val 1

Alarm

Options:

Val 0
Val 1
Val 2
Val 3
Val 4

Ignore
Alarm
FltCoastStop
FltRampStop
FltCurLimStp

File:
Group:

Utility
Fault/Alm Config

373

Motor Stall Time
Enter or write a value to specify the time delay between when
the drive detects a “Motor Stall” condition and when it
declares the exception evet.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Sec
5
0.1
3000
Linkable, Read-Write, Floating Point
Utility
Fault/Alm Config

374

Motor Stall Cnfg
Enter a value to configure the drive's response to a “Motor
Stall” exception event.

• Value 0 - Ignore configures the drive module to

continue running as normal, in response to this event

• Value 1 - Alarm configures the drive module to set the

appropriate alarm bit in response to this event

• Value 2 - FltCoastStop configures the drive module to

perform a coast stop and set the appropriate fault bit in
response to this event

Default

Val 0

Ignore

Options:

Val 0
Val 1
Val 2

Ignore
Alarm
FltCoastStop

File:
Group:

Utility
Fault/Alm Config

No.

Name
Description

Values