Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 133

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-53

175

Setpt 2 Data
Provides data for comparison to parameter 177 [Setpt2
TripPoint], driving bit 17 [Above Setpt 2] of parameter 155
[Logic Status].

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0
-8
8
Linkable, Read-Write, Floating Point
Speed Control
Setpoint Monitor

Positive Setpoint (Parameter 176 [Setpt 2 TripPoint] Greater Than Zero)

Negative Setpoint (Parameter 176 [Setpt 2 TripPoint] Less Than Zero)

176

Setpt2 TripPoint
Provides the midpoint for operation of bit 16 [At Setpt 1] of
parameter 155 [Logic Status].

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0.2
-8
8
Linkable, Read-Write, Floating Point
Speed Control
Setpoint Monitor

No.

Name
Description

Values

P176 [Setpt 2 TripPoint] - P177 [Setpt 2 Limit]

P175 [Setpt 2 Data]

bit 17 [Abo

ve

Setpt 2] tur

ns on

bit 17 [Abo

ve

Setpt 2] tur

ns off

0

Time

P176 [Setpt 2 TripPoint]

P175 [Setpt 2 Data]

bit 17 [Abo

ve

Setpt 2] tur

ns on

bit 17 [Abo

ve

Setpt 2] tur

ns off

0

P176 [Setpt 2 TripPoint] - P177 [Setpt 2 Limit]

P176 [Setpt 2 TripPoint]

Time