Parameter 326 [alarm status 1, Parameter 327 [alarm status 2 – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 242

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

B-162 1756-DMD30 Specific Information

Parameter 326 [Alarm Status 1]

This parameter indicates the occurance of exception events that have
been configured as alarm conditions. These events are from
parameter 320 [Exception Event1].

Parameter 327 [Alarm Status 2]

This parameter indicates the occurance of exception events that have
been configured as alarm conditions. These are the same events
shown in parameter 321 [Exception Event 2].

Bit

Fault Name

Fault Description

Bit 0

Abs OverSpd

Motor speed has exceed the value in Parameter 335 [Abs
OverSpd Lim].

Bit 1

SpdRef Decel

The drive has failed to achieve a zero speed condition.

Bit 6

Ctrl EE Mem

Not Used

Bit 7

SLink HW

Not Used

Bit 8

SLink Comm

A SynchLink communication failure has occurred. These
faults are enumerated in parameter 1229 [SL Error Status].

Bit 10

Mtr OL Trip

A Mtr OL Trip exception event has alarmed the drive module.
Refer to parameter 371 [Mtr OL Trip Cnfg], parameter 336
[Service Factor], parameter 337 [Mtr I2T Curr Min], and
parameter 338 [Mtr I2T Spd Min].

Bit 11

Mtr OL Pendg

A Mtr OL Pendg exception event has alarmed the drive
module. Refer to parameter 372 [Mtr OL Pend Cnfg],
parameter 336 [Service Factor], parameter 337 [Mtr I2T Curr
Min], and parameter 338 [Mtr I2T Spd Min].

Bit 12

Motor Stall

A motor stall has lasted longer than the time specified by
parameter 373 [Motor Stall Time]. This has alarmed the
drive module. Refer to parameter 374 [Moter Stall Cnfg].

Bit 18

DSP Mem Err

Flash memory does not match the SRAM memory.

Bit 19

DSP Err

The drive has failed to complete DSP (VPL) interrupt tasks in
the allotted time.

Bit

Fault Name

Fault Description

7

Slink Mult

SynchLink Multiply failure has occurred. These faults are
enumerated in parameter 1034 [SL Mult State].

26

Drv Fault

A motor control fault event has occurred. Motor control
faults are enumerated in parmeter 2122 [MC Faults].

27

Drv Warning

A motor control warning event has occured. Motor control
warnings are enumerated in parmeter 2123 [MC Warnings].

28

Lgx OutOfRun

The Logix Controller is out of the run mode.

Advertising