Publication 1756-UM522B-EN-P - February 2003

B-54 1756-DMD30 Specific Information

177

Setpt 2 Limit
Creates a tolerance - hysteresis band around the value in
parameter 176 [Setpt2 TripPoint]. For positive setpoints:
Turn-on level = TripPoint, Turn-off level = TripPoint - Limit. For
negative setpoints: Turn-on level = TripPoint, Turn-off level =
TripPoint + Limit.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0.01
0
0.5
Linkable, Read-Write, Floating Point
Speed Control
Setpoint Monitor

180

PI Output
The final output of the Process Control regulator. A value of 1
can represent either base motor speed, motor rated torque, or
100% for some external function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0
-8
8
Non-Linkable, Read Only, Floating Point
Process Control
Regulator

181

PI Reference
The reference input for the process control regulator. A value
of 1 can represent either base motor speed, motor rated
torque, or 100% for some external function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0
-8
8
Linkable, Read-Write, Floating Point
Process Control
Process Config

182

PI Feedback
The feedback input for the process control regulator. A value
of 1 can represent either base motor speed, motor rated
torque, or 100% for some external function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0
-8
8
Linkable, Read-Write, Floating Point
Process Control
Process Config

No.

Name
Description

Values