Publication 1756-UM522B-EN-P - February 2003

1756-DMF30 Specific Information C-89

2131

FML Feedback
Displays measured field current. A value of 4095 indicates hot
field current - equal to the value of parameter 2185 [Hot Field
Curr].

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0
-4095
4095
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback

2132

Field Amps Fdbk
Displays measured field current in Amps x 10, (e.g., a value of
501 indicates 50.1A).

Units:
Default:
Min:
Max:
Type:
File:
Group:

Amps
0
-32768
32767
Non-Linkable, Read-Only, Floating Point
DPS/PMI
Feedback

2133

Field Volt Fdbk
Displays the field voltage feedback value, in volts. This voltage
is calculated based on the AC line voltage and field firing
angle.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Volt
0
-32768
32767
Non-Linkable, Read-Only, Floating Point
DPS/PMI
Feedback

2134

User Anlg Input
Displays the measured user analog input value from the
Resolver Feedback connector on the Resolver & Drive l/O
module. This value may be accessed through the PMI meter
ports.

Default:
Min:
Max:
Type:
File:
Group:

0
-2048
2048
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback

2135

Res Scan Posit
Displays the electrical position of the resolver (if used). This
register is reset to zero at power-up.

Default:
Min:
Max:
Type:
File:
Group:

0
-32768
32767
Non-Linkable, Read-Only, 16-Bit Integer
Speed/Posit Fdbk, DPS/PMI
Resolver, Feedback

2136

Res Strobe Posit
Displays the electrical position of the resolver at the time a
strobe signal is detected.

Default:
Min:
Max:
Type:
File:
Group:

0
-32768
32767
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback

2149

NV Faults
Non Volatile storage location for internal module faults.
Rockwell development personnel may use the value in this
register to debug the module firmware.

Default:
Min:
Max:
Type:
File:
Group:

0
0
4294967296
Non-Linkable, Read-Only, 32-Bit Integer
DPS/PMI
Feedback

2150

CML Crossovr Frq
Enter a value to determine the response of the current minor
loop. Higher values improve response. However, higher
values may degrade stability.

Units:
Default:
Min:
Max:
Type:
File:
Group:

R/S
200
0
400
Linkable, Read-Write, 16-Bit Integer
DPS/PMI
Regulator Config

No.

Name
Description

Values