Publication 1756-UM522B-EN-P - February 2003

B-56 1756-DMD30 Specific Information

186

PI Prop Gain
Controls the proportional gain of the Process Control regulator.
If the proportional gain is 1.0, the regulator output equals 1 pu
for 1 pu error.

Default:
Min:
Max:
Type:
File:
Group:

8
0
200
Linkable, Read-Write, Floating Point
Process Control
Regulator

187

PI Integ Time
Controls the integral gain of the Process Control regulator. If
the integrator time is 1.0, the regulator output equals 1 pu in 1
second for 1 pu error.

Units:
Default:
Min:
Max:
Type:
File:
Group:

/Sec
8
0
4095.8
Linkable, Read-Write, Floating Point
Process Control
Regulator

188

PI Integ HLim
The high limit of the integral gain channel for the Process
Control regulator. A value of 1 can represent either base motor
speed, motor rated torque, or 100% for some external
function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0.1
0
8
Linkables Read-Write, Floating Point
Process Control
Regulator

189

PI Integ LLim
The low limit of the integral gain channel for the Process
Control regulator. A value of 1 can represent either base motor
speed, motor rated torque, or 100% for some external
function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
-0.1
-8
0
Linkable, Read-Write, Floating Point
Process Control
Regulator

190

PI Integ Output
Displays the output value of the integral channel of the
Process Control regulator. A value of 1 can represent either
base motor speed, motor rated torque, or 100% for some
external function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0
-8
8
Non-Linkable, Read Only, Floating Point
Process Control
Regulator

191

PI High Limit
The high limit of the Process Control regulator output. A value
of 1 can represent either base motor speed, motor rated
torque, or 100% for some external function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0.1
0
8
Linkable, Read-Write, Floating Point
Process Control
Regulator

192

PI Lower Limit
The low limit of the Process Control regulator output. A value
of 1 can represent either base motor speed, motor rated
torque, or 100% for some external function.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
-0.1
-8
0
Linkable, Read-Write, Floating Point
Process Control
Regulator