Publication 1756-UM522B-EN-P - February 2003

1756-DMF30 Specific Information C-101

Parameter 324 [Fault Status 2]

This parameter indicates the presence of certain drive anomolies that
caused the drive to fault (stop). These are the same events shown in
parameter 321 [Exception Event 2]. These bits are latched until they
are reset by setting bit 19 [Clear Fault] of parameter 152 [Applied
LogicCmd]. After turning the Clear Fault bit on, the drive may be
re-started after turning the command bits off and then back on again.
If the fault conditions still exist, the identifying bit in this parameter
will immediately be set again. The fault conditions reported in this
register result in turning off the drive.

Bit

Fault Name

Fault Description

7

Slink Mult

SynchLink Multiply failure has occurred. These
faults are enumerated in parameter 1034 [SL Mult
State].

26

Drv Fault

A motor control fault event has occurred. Motor
control faults are enumerated in parmeter 2122 [MC
Faults].

27

Drv Warning

A motor control warning event has occured. Motor
control warnings are enumerated in parmeter 2123
[MC Warnings].

28

Lgx OutOfRun

The Logix Controller is out of the run mode

29

Lgx Timeout

Communications with the Logix Controller has timed
out

30

Lgx Closed

The Logix Controller has closed a connection to the
Drive Module

31

Lgx LinkChng

A required parameter link relating to a
communications connection has been modified