Parameter 1229 [sl error status – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 243

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-163

Parameter 1229 [SL Error Status]

This parameter indicates the occurance of SynchLink errors.

29

Lgx Timeout

Communications with the Logix Controller has timed out.

30

Lgx Closed

The Logix Controller has closed a connection to the Drive
Module.

31

Lgx LinkChng

A required parameter link relating to a communications
connection has been modified.

Bit

Fault Name

Fault Description

0

Sync Loss

SynchLink communication has failed, after it had been
established.

1

Rx Loss

The receive port is not receiving data, and the receive port
configuration is set to receive data.

2

Many BOF Err

The number of BOF (Beginning Of Frame) errors accumulated
in parameter 1232 [SL BOF Err Accum] exceeds the value in
parameter 1235 [SL BOF Err Limit].

3

Many CRC Err

The number of CRC (Cycling Ring Checksum) errors
accumulated in parameter 1230 [SL CRC Err Accum] exceeds
the value in parameter 1234 [SL CRC Err Limit].

4

Pckg Msg Err

The received package sequence number has not matched for
1.0 S.

5

CommForm Err

The format of received data does not match the
configuration of the receive port.

6

Sys Rev Err

The system revision in received data does not match the
value of parameter 1001 [SynchLink Rev].

7

Mult TKeeper

More than one node on the SynchLink system is configured
as a Time Keeper.

Bit

Fault Name

Fault Description

Advertising