Publication 1756-UM522B-EN-P - February 2003

B-70 1756-DMD30 Specific Information

330

Fault TP Data
Displays the data selected by parameter 329 [Fault TP Sel].

Units:
Default:
Min:
Max:
Type:
File:
Group:

0
0
-2200000000
2200000000
Non-Linkable
Read Only
Floating Point
Utility
Test Points

335

Abs OverSpd Lim
Sets an incrmental speed above parameter 31 [Fwd Speed
Limit] and below parameter 30 [Rev Speed Limit] that is
allowable before the drive indicates its speed is out of range.

Units:
Default:
Min:
Max:
Type:
File:
Group:

RPM
350
0
1750
Non-Linkable, Read-Write, Floating Point
Dynamic Control
Dynamic Control

336

Service Factor
Sets the minimum level of current that causes a motor
overload trip under continuous operation. Current levels below
this value will not result in an overload trip. For example, a
service factor of 1.15 implies continuous operation up to 115%
of nameplate motor current.

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
1.15
1
2
Non-Linkable, Read-Write, Floating Point
Dynamic Control
Overload Protect

337

Mtr I2T Curr Min
Sets the minimum current threshold for the motor overload
(I

2

T) function. The value indicates minimum current at the

minimum speed, parameter 338 [Mtr I2T Spd Min], and these
are the first current/speed breakpoint. From this point the
current threshold is linear to the value specified by parameter
336 [Service Factor].

Units:
Default:
Min:
Max:
Type:
File:
Group:

P.U.
0.5
0.05
1
Non-Linkable, Read-Write, Floating Point
Dynamic Control
Overload Protect

No.

Name
Description

Values

Advertising