C-88 1756-DMF30 Specific Information

2124

Pwr DeviceStatus
Indicates which SCR has shorted or not firing. If an SCR is
shorted, bit 0 [SCR Fault] of parameter 2122 [MC Faults] will be
set. If an SCR is not firing correctly, bit 0 [BrdgNotFirng] of
parameter 2123 [MC Warnings]will be set.
For a regenerative drive, this parameter indicates the pair of
SCRs that has faulted. For a non-regenerative drive, this
parameter indicates the specific SCR that has faulted.
The bits of this parameters are set when a fault event is
detected. They stay latched until bit 19 [Clear Fault] of
parameter 152 [AppliedLogic Cmd] or bit 19 [Clr Drv Wrn] of
parameter 166 [Motor Ctrl Cmmd] is set. If the fault event
remains present, the identifying bit is set again.

Default:

0000 0000 0000 0000

Options

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

SCR 1 Fault
SCR 2 Fault
SCR 3 Fault
SCR 4 Fault
SCR 5 Fault
SCR 6 Fault
SCR 11 Fault
SCR 12 Fault
SCR 13 Fault
SCR 14 Fault
SCR 15 Fault
SCR 16 Fault
Reserved
Reserved
Reserved
Reserved

File:
Group:

Utility, DPS/PMI
Diagnostics, Feedback

2125

Interlock Code
The PMI processor performs interlock tests in response to
parameter 2100 [Drive Ctrl Word]. If any of the diagnostics
fail the PMI processor sets the bit in parameter 2125 [Interlock
Code] that corresponds to the first failed diagnostic. The bit
stays latched until bit 19 [Clear Fault] of parameter 152
[Applied LogicCmd] or bit 19 [Clr Drv Wrn] of parameter 166
[Motor Ctrl CÌmd] is set. Refer to Reliance Electric publication
S-3001-1, Distributed Power System SD3000 Drive
Diagnostics, Troubleshooting and Start-Up Guidelines, for
information about the interlock diagnostics.

Default:

0000 0000 0000 0000

Options

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15

Bad CML Req
3PhPrmNotLod
3PhGnsNotLod
3PhFlt RstRq
RPI Missing
Fld Not Rdy
Fld NotAlwd
M-Con NotCls
Bad FML Req
F Par NotLod
F Gns NotLod
F Flt Rst Rq
Reserved
Reserved
F FB or Cfg
Reserved

File:
Group:

Utility, DPS/PMI
Diagnostics, Feedback

2126

AC Line Volt FB
Displays the measured AC RMS line voltage in volts.

Units:
Default:
Min:
Max:
Type:
File:
Group:

Volt
0
0
1000
Non-Linkable, Read-Only, Floating Point
DPS/PMI
Feedback

2127

3Ph Feedback
Displays measured three-phase current. A value of 4095
indicates maximum positive current - equal to the value of
parameter 122 [Curr PosLim Actl]. A value of -4095 indicates a
maximum negative current - equal to the value of parameter
121 [Curr NegLim Actl].

Default:
Min:
Max:
Type:
File:
Group:

0
-4095
4095
Non-Linkable, Read-Only, 16-Bit Integer
DPS/PMI
Feedback

No.

Name
Description

Values