Module-defined data tags, Fault and alarm window – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 33

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

Drive Module Features

3-7

to direct data in a daisy chain configuration, In order to pass-through
buffered data, the local controller must intervene to move data along.

Module-Defined Data Tags

When you create a module, module-defined data types and tags are
created in the RSLogix 5000 programming software. These tags allow
you to access the Input and Output Data of the module via the
controller’s ladder logic, if necessary

The types of tags created vary, depending on which communications
format you choose when creating a module. There are two types of
tags:

Input Data Tags

Output Data Tags

Table 3.A
Drive Module Receive Communications Formats

Receive Port Communications Format

Transfer Rate (across the fiber optic
cable) for Each Data Type:

2 Direct Words, 18 Buffered

Direct Data - Updated every 50

µ

S

Buffered Data - Updated every 250

µ

S

4 Direct Words, 18 Buffered

Direct Data - Updated every 50

µ

S

Buffered Data - Updated every 500

µ

S

4 Direct Words, 8 Buffered

Direct Data - Updated every 50

µ

S

Buffered Data - Updated every 250

µ

S

No Receive Data

No data updated in this format

Table 3.B
Drive Module Transmit Communications Formats

Transmit Port Communications Format

Transfer Rate (across the fiber optic
cable) for Each Data Type:

2 Direct Words, 18 Buffered

Direct Data - Updated every 50

µ

S

Buffered Data - Updated every 250

µ

S

4 Direct Words, 18 Buffered

Direct Data - Updated every 50

µ

S

Buffered Data - Updated every 500

µ

S

4 Direct Words, 8 Buffered

Direct Data - Updated every 50

µ

S

Buffered Data - Updated every 250

µ

S

Listen Only, No Transmit Data

No data updated in this format

No Transmit Data

No data updated in this format