Parameter 2125 [interlock code – Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 361

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

1756-DMF30 Specific Information C-109

Parameter 2125 [Interlock Code]

The PMI processor performs interlock tests in response to parameter
2100 [Drive Ctrl Word]. If any of the diagnostics fail the PMI
processor sets the bit in parameter 2125 [Interlock Code] that
corresponds to the first failed diagnostic. The bit stays latched until
bit 19 [Clear Fault] of parameter 152 [Applied Logic Cmd] or bit 19 [Clr
Drv Wrn] of parameter 166 [Motor Ctrl Cmd] is set. Refer to Reliance
Electric publication S-3001-1, Distributed Power System SD3000 Drive
Diagnostics, Troubleshooting and Start-Up Guidelines
, for information
about the interlock diagnostics.

10

SCR 14 Fault

SCR 14 Fault (Reverse Bridge)

11

SCR 15 Fault

SCR 15 Fault (Reverse Bridge)

12

SCR 16 Fault

SCR 16 Fault (Reverse Bridge)

Bit

Fault Name

Fault Description

0

Bad CML Req

More than one incompatible CML operating mode has
been requested at a time in parameter 166 [Motor Ctrl
Cmmd]. The following operating modes are mutually
exclusive:

•••• Armature Alpha Test

•••• Armature Identification Test

•••• CML Run

This bit is also set if you have attempted to restart the
drive without resetting the appropriate command bits
from parameter 166. Note that the bits in register 166
are edge-sensitive.

1

3PhPrmNotLod

Three-phase configuration parameters have not been
downloaded into the PMI module from the Drive
Module

2

3PhGnsNotLod

Three-phase configuration parameters have not been
downloaded into the PMI module from the Dive
Module.

3

3PhFltRstRq

The CML Faults Need to be Reset bit is set if previous
armature faults (parameter 2122 [MC Faults]) have not
been cleared.

4

RPI Missing

The run permissive input on the Resolver & Drive l/O
module is not on.

5

Fld Not Rdy

The single-phase field is not on. Note that the CML
can-not be executed if the field is not on.

6

Fld NotAlwd

The single-phase field has been requested when the
armature identification test or the armature alpha test
is running.

7

M-Con NotCls

The M-Contactor did not close at the expected time.

Bit

Fault Name

Fault Description