Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 338

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

C-86 1756-DMF30 Specific Information

2106

PMI D/A Output
The value in the PMI D/A Output register is transmitted to the
PMI Processor. The value can then be displayed on one of the
four PMI Processor meter ports. This register can contain any
variable in the system as long as it is a 16-bit integer. Floating
point or double-integer values cannot be displayed on the PMI
Processor’s D/A meter ports.

Default:
Min:
Max:
Type:
File:
Group:

0
-32768
32767
Linkable, Read-Write, 32-Bit Integer
DPS/PMI
Commands

2122

MC Faults
Indicates Motor-Control faults. These bits latch when a
Motor-Control fault event occurs. They stay latched until bit
19 [Clear Fault] of parameter 152 [Applied LogicCmd] or bit 19
[Clr Drv Wrn] of parameter 166 [Motor Ctrl Cmmd] is set. If the
fault condition remains present, the identifying bit is set again.

Default:

0000 0000 0000 0000 0000 0000 0000 0000

Options

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bti 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 16
Bit 17
Bit 18
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit 24
Bit 25
Bit 26
Bit 27
Bit 28
Bit 29
Bit 30
Bit 31

SCR Fault
Reserved
Reserved
AC Line Sync
InstOvr Curr
Reserved
Field Loss
Reserved
TachWire Opn
ResolverCard
Reserved
PwrTech Card
PMI Pwr Sply
PMI Bus
Reserved
PMI CommLoss
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

File:
Group:

Utility, DPS/PMI
Diagnostics, Feedback

No.

Name
Description

Values