C-104 1756-DMF30 Specific Information

Parameter 2044 [Rail Port 0 Faults]

This parameter indicates the occurance of faults associtated with Rail
I/O on Port 0.

Bit

Fault Name

Fault Description

0

Ch0 OvrRange

Analog input on channel 0 is over the maximum
value.

(1)

(1)

Analog 4 input 4-20 mA (model number 61C345) maximum value = 22.1 mA
Analog 4 input 0-10V (model number 61C346) maximum value = 11.3V
Analog 2 input / 2 ouput 4-20 mA (model number 61C345) maximum value = 22.6 mA
Analog 2 input / 2 ouput 0-10V (model number 61C346) maximum value = 11.3V

1

Ch0 UndRange

Analog input on channel 0 is under the minimum
value.

(2)

(2)

Analog 4 input 4-20 mA (model number 61C345) minimum value = 2.4 mA
Analog 4 input 0-10V (model number 61C346) minimum value = -1.0V
Analog 2 input / 2 ouput 4-20 mA (model number 61C345) minimum value = 2.5 mA
Analog 2 input / 2 ouput 0-10V (model number 61C346) minimum value = -1.0V

2

Ch1 OvrRange

Analog input on channel 1 is over the maximum
value.

(1)

3

Ch1 UndRange

Analog input on channel 1 is under the minimum
value.

(2)

4

Ch2 OvrRange

Analog input on channel 2 is over the maximum
value.

(1)

5

Ch2 UndRange

Analog input on channel 2 is under the minimum
value.

(2)

6

Ch3 OvrRange

Analog input on channel 3 is over the maximum
value.

(1)

7

Ch3 UndRange

Analog input on channel 3 is under the minimum
value.

(2)

8

Port NotCntd

No device is connected to the port, which is
configured to accept a device.

9

Bad ID

A device other than a rail is plugged into the port.

10

Bad Chk Bits

Bad rail communication check bits have been
received.

11

IO NotRdy

The I/O interface is not ready.