Rockwell Automation 1756-DMF30 ControlLogix Drive Module User Manual

Page 209

Advertising
background image

Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-129

1228

SL Error History
Displays SynchLink faults which have occurred since the last
fault clear or power cycle.

• Bit 0 [Sync Loss] indicates SynchLink communication

has failed, after it had been established

• Bit 1 [Rx Loss] indicates the receive port is not

receiving data, and the receive port configuration is set
toeceive data

• Bit 2 [Many BOF Err] indicates the number of Beginning

Of Frame (BOF) errors exceeds limit set by parameter
1235 [SL BOF Err Limit]

• Bit 3 [Many CRC Err] indicatesindicates the number of

Cyclic Redundancy Check (CRC) errors exceeds limit set
by parameter 1234 [SL CRC Err Limit]

• Bit 4 [Pckg Msg Err] indicates the received package

sequence number has not matched for 1.0S

• Bit 5 [CommForm Err] indicates the format of received

data does not match the configuration of the receive
port

• Bit 6 [Sys Rev Err] indicates the system revision in the

received data does not match the value of parameter
1001 [SynchLink Rev]

• Bit 7 [Mult TKeeper] indicates more than one node on

the SynchLink system is configured as a time keeper

Default:

0000 0000 0000 0000 0000 0000 0000 0000

Options:

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Bit 16
Bit 17
Bit 18
Bit 19
Bit 20
Bit 21
Bit 22
Bit 23
Bit 24
Bit 25
Bit 26
Bit 27
Bit 28
Bit 29
Bit 30
Bit 31

Sync Loss
Rx Loss
Many BOF Err
Many CRC Err
Pckg Msg Err
CommForm Err
Sys Rev Err
Mult TKeeper
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved