Publication 1756-UM522B-EN-P - February 2003

1756-DMD30 Specific Information B-169

Parameter 2124 [Pwr Device Status]

The bits of this parameter indicate which SCR has shorted or not
firing. If an SCR is shorted parameter 2122 [MC Faults] bit 0 [SCR
Fault] will be set. If an SCR is not firing correctly parameter 2123 [MC
Warnings] bit 0 [BrdgNotFirng]will be set.

For a regenerative drive, this parameter indicates the pair of SCRs that
has faulted. For a non-regenerative drive, this parameter indicates the
specific SCR that has faulted.

The bits of this parameters are set when a fault event is detected.
They stay latched until bit 19 [Clear Fault] of parameter 152 [Applied
Logic Cmd] or bit 19 [Clr Drv Wrn] of parameter 166 [Motor Ctrl Cmd]
is set. If the fault event remains present, the identifying bit is set
again.

Bit

Fault Name

Fault Description

0

SCR 1 Fault

SCR 1 Fault (Forward Bridge)

1

SCR 2 Fault

SCR 2 Fault (Forward Bridge)

3

SCR 3 Fault

SCR 3 Fault (Forward Bridge)

4

SCR 4 Fault

SCR 4 Fault (Forward Bridge)

5

SCR 5 Fault

SCR 5 Fault (Forward Bridge)

6

SCR 6 Fault

SCR 6 Fault (Forward Bridge)

7

SCR 11 Fault

SCR 11 Fault (Reverse Bridge)

8

SCR 12 Fault

SCR 12 Fault (Reverse Bridge)

9

SCR 13 Fault

SCR 13 Fault (Reverse Bridge)

10

SCR 14 Fault

SCR 14 Fault (Reverse Bridge)

11

SCR 15 Fault

SCR 15 Fault (Reverse Bridge)

12

SCR 16 Fault

SCR 16 Fault (Reverse Bridge)