Flowserve Logix MD+ ValveSight User Manual

Page 105

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

105



Training Status
Training Status is present on this page because one or more fields or graphs shows data
that was gathered during the training process. The field shows one of the following states:

Training Enabled - which indicates system data is being recorded. Training should

run during normal system behavior.

Training Disabled - which indicates NO system data is being recorded.

Training Complete which indicates that the time period for training has expired and

the data is stored in the positioner.

NOTE: The Training function requires the Pro positioner upgrade level (522MD+).


Action Buttons
The Apply button will save changes to the connected device.


The Retrieve button will retrieve the latest information from the device.


Warning and Alarms

Actuator Cycles

Definition: The actuator cycle limit has been exceeded.

Implications: Each cycle represents two reversals of the direction of

actuator movement. The cycle counting criterion and count limit are set
by the user to track the usage of the actuator.

Possible Solutions: Follow routine procedures for maintenance when

the limit is reached such as checking the packing tightness, and
checking linkages for wear, misalignment, and tightness. After
maintenance, reset the cycle accumulator.

Actuator Travel

Definition: The total accumulated actuator travel limit has been

exceeded.

Implications: The travel is accumulated in both directions. The travel

counting criterion and limit are set by the user to track the usage of the
actuator.