ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

64


mechanical obstruction, loosen the packing, clean the stem, repair or
replace the actuator, repair the valve if galling is suspected.

Closed Too Far

Definition: The valve has closed farther than it did at the last calibration

Implications: While the valve was in use, it closed farther than it did at

the last calibration by 0.5%.

Possible Solutions: Check the feedback arm linkage and ensure the

valve stem connection is tight. Recalibrate the stroke. If the process
cannot be interrupted a service technician may be able to adjust the
calibration.

Opened Too Far

Definition: The valve has opened farther than it did at the last

calibration

Implications: While the valve was in use, it opened farther than it did at

the last calibration by 0.5%.

Possible Solutions: Check the feedback arm linkage and ensure the

valve stem connection is tight. Recalibrate the stroke. If the process
cannot be interrupted a service technician may be able to adjust the
calibration.