Flowserve Logix MD+ ValveSight User Manual

Page 125

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

125



Action Buttons
The Apply button will save changes to the connected device.


The Retrieve button will retrieve the latest information from the device.

Warnings and Alarms

Position Frequency

Definition: The frequency of the position signal is above the warning or

alarm limit. The positioner is controlling the position of the valve with
rapid corrections.

Possible Solutions: Verify the limits are set at an appropriate level.

Adjust the selectable Gain switch to a lower setting or use the "Hi
Friction" setting. Perform a QUICK-CAL which sets the gains based on
valve response. Check for high friction. If the problem persists replace
the relay.

Advertising
This manual is related to the following products: