Flowserve Logix MD+ ValveSight User Manual

Page 50

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

50


Possible Solutions: Check linkages and air supply to make sure the

system is properly connected. If the time out occurred because the
actuator is very large then simply retry the QUICK-CAL and the
positioner will automatically adjust for a larger actuator by doubling the
time allowed for movement. This error may be cleared by briefly
pushing the QUICK-CAL/ACCEPT.

Settle Time Out

Definition: During calibration, the position feedback sensor showed

movement, but did not settle.

Possible Solutions: Check for loose linkages or a loose positioner

sensor. This error may appear on some very small actuators during the
initial calibration. Recalibrating may clear the problem, or this error may
be cleared by briefly pushing the QUICK-CAL/ACCEPT button.

ILO Time Out

Definition: During calibration the Inner Loop Offset (ILO) value did not

settle. This could result in less accurate positioning.

Possible Solutions: Repeat the stroke calibration to get a more

accurate ILO value. To proceed using the less accurate ILO value, this
error may be cleared by briefly pushing the QUICK-CAL/ACCEPT
button. Lowering the setting on the gain selection switch may help if the
actuator is unstable during the calibration.

AO Range Small

Definition: During an Analog Output Calibration the difference between

the milliamp signal at 0% and the milliamp signal at 100% was too
small.

Possible Solutions: Recalibrate making sure to use a larger difference

between signal limits. This notification can be cleared by briefly
pressing the QUICK-CAL/ACCEPT button.

Command Range Small

Definition: During a Command Loop Calibration, the difference

between the signal at 0% and the signal at 100% was too small. The
system is designed to accept a difference greater than 5 mA.

Possible Solutions: Recalibrate making sure to use a larger

difference between command signal limits. The difference must exceed
5 mA.

Command < ADC Range

Definition: During Command Loop Calibration, the 0% signal was out

of the Analog to Digital Converter (ADC) range.

Possible Solutions: The system is designed to accept a signal that is

above 10 ADC counts. Recalibrate making sure the ADC counts are
above that limit.

Command > ADC Range

Definition: During Command Loop Calibration, the 100% signal was

out of the Analog to Digital Converter (ADC) range.

Possible Solutions: The system is designed to accept a signal that is

below 4085 ADC counts. Recalibrate making sure the ADC counts are

Advertising
This manual is related to the following products: