user in many cases) determine the conditions when the color will turn from
green to yellow to red. The most sever of the indicators on this page will be
shown in the health bar on the Dashboard.

Dark Green

circle indicates a healthy condition where no attention is

needed.

Light Green

indicates an occurrence of a normal activity that does

not affect the health of the valve system.

Yellow

circle indicates that an active warning, alert or mode is

present.

Red

circle indicates that an active alarm or state is present that

could seriously limit the operation of the valve.

Gray

circle indicates that the feature or condition is not available

because the configuration of the hardware or software does not support
it.

A checkbox indicates the masked status. Check to mask. If a particular

indicator is masked, it will not be shown in the active indicator field at the top
of each screen, affect the status of the health bars on the main dashboard, be
sent in command 48, or be seen on the blinking LEDs on the positioner. It
will however continue to show on this page.

Start Up Status

Initializing

Definition: The positioner has powered up and is displaying a blink

sequence 3 times.

Possible Solutions: Wait for 3 blink sequences to complete.

Stroke Calibration Required

Definition: A factory reset was performed and the positioner has not

yet been calibrated. The unit will not respond to commands and will
remain in the fail-safe position until a calibration is successfully
completed.

Possible Solutions: Perform a Stroke Calibration (QUICK-CAL) by

holding the QUICK-CAL/ACCEPT button down for 3 seconds, or
perform a Pressure or Friction calibration if desired. See the Calibration
section of the IOM for warnings.