ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

213


the Abort button

A/O Calibration in Progress

Definition: The analog output calibration sequence is in progress.

Possible Solutions: The calibration can be canceled from the Sensor

Calibration page of the DTM, from the handheld, or by briefly pressing
the Abort button

Jog Calibration in Progress

Definition: During a jog calibration, the unit is waiting for the user to

manually adjust the valve position to the desired 100% open position.

Possible Solutions: Use the Up and Down buttons on the positioner to

adjust the valve to the desired fully open position. The QUICK-
CAL/ACCEPT button to accept.