ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

110


Possible Solutions: Set the limit to a lower or higher value if more

travel is needed, or adjust the command signal back in the specified
range.

Command Frequency

Definition: The frequency of the command signal is above the warning

or alarm limit. This could mean the control loop is oscillating faster than
normal.

Possible Solutions: Verify the limits are set at an appropriate level.

Review the control loop parameters and equipment. Adjust as
necessary.

Command Amplitude

Definition: The amplitude of the command signal is above the warning

or alarm limit. This could mean the control loop has larger swings than
desirable.

Possible Solutions: Verify the limits are set at an appropriate level.

Review the control loop parameters and equipment. Adjust as
necessary.

Position Frequency

Definition: The frequency of the position signal is above the warning or

alarm limit. The positioner is controlling the position of the valve with
rapid corrections.

Possible Solutions: Verify the limits are set at an appropriate level.

Adjust the selectable Gain switch to a lower setting or use the "Hi
Friction" setting. Perform a QUICK-CAL which sets the gains based on
valve response. Check for high friction. If the problem persists replace
the relay.

Position Amplitude

Definition: The amplitude of the position signal is above the warning

limit. The positioner is controlling the position of the valve with large
corrections.

Possible Solutions: Verify the limits are set at an appropriate level.

Adjust the selectable Gain switch to a lower setting or use the "Hi
Friction" setting. Perform a QUICK-CAL which sets the gains based on
valve response. Check for high friction. If the problem persists replace
the relay.