Flowserve Logix MD+ ValveSight User Manual

Page 84

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

84



Positioner Humidity
The Positioner Humidity box displays a scale with the actual positioner humidity and the Air
Supply Humid Warning limit. The humidity warning limit is not user settable and will be
triggered according to the rules below.

•

Temperature is less than 35 F (1.7 C) and RH > 80%.

•

Temperature is between 35 and 40 F(1.7-4.4 C) and RH > 70%.

•

Temperature is between 40 and 45 F(4.4-7.2 C) and RH > 60%.

•

Temperature is above 45 F(7.2 C) and RH > 50%.


Warnings and Alarms

Temperature High

•

Definition: The temperature of the internal electronics has exceeded

the manufacturer set limit of 85°C (176°F). High temperature may affect
performance or limit the life of the positioner.

•

Possible Solutions: Regulate the temperature of the positioner by

shading or cooling supply gas. If the temperature reading is in error,
replace the main board.

Temperature Low

•

Definition: The temperature of the internal electronics has exceeded

the manufacture set limit of -40°C (-40°F). Low temperature may inhibit
responsiveness and accuracy.

•

Possible Solutions: Regulate the temperature of the positioner. If the

temperature reading is in error, replace the main circuit board.

Air Supply Humid

•

Definition: The supply gas has high relative humidity which can lead to

condensation on electronic components and failure of electronic
functions.

•

Possible Solutions: Ensure supply gas is clean and dry. Check and

clean the regulator filter.