Positioner Humidity
The Positioner Humidity box displays a scale with the actual positioner humidity and the Air
Supply Humid Warning limit. The humidity warning limit is not user settable and will be
triggered according to the rules below.

Temperature is less than 35 F (1.7 C) and RH > 80%.

Temperature is between 35 and 40 F(1.7-4.4 C) and RH > 70%.

Temperature is between 40 and 45 F(4.4-7.2 C) and RH > 60%.

Temperature is above 45 F(7.2 C) and RH > 50%.


Warnings and Alarms

Temperature High

Definition: The temperature of the internal electronics has exceeded

the manufacturer set limit of 85°C (176°F). High temperature may affect
performance or limit the life of the positioner.

Possible Solutions: Regulate the temperature of the positioner by

shading or cooling supply gas. If the temperature reading is in error,
replace the main board.

Temperature Low

Definition: The temperature of the internal electronics has exceeded

the manufacture set limit of -40°C (-40°F). Low temperature may inhibit
responsiveness and accuracy.

Possible Solutions: Regulate the temperature of the positioner. If the

temperature reading is in error, replace the main circuit board.

Air Supply Humid

Definition: The supply gas has high relative humidity which can lead to

condensation on electronic components and failure of electronic
functions.

Possible Solutions: Ensure supply gas is clean and dry. Check and

clean the regulator filter.