ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

82


warning, or CPU usage warning.

Possible Solutions: If the problem persists, perform a factory reset. If

it still persists, reprogram or replace the main board.

Memory Error

Definition: The microprocessor's memory has a problem.

Possible Solutions: Error may clear with time. If error persists, cycle

power and complete a QUICK-CAL. If the error still persists, perform a
factory reset, reprogram or replace the main circuit board.

Air Supply Icing

Definition: The supply gas has high relative humidity and the

temperature is close to 0 °C (32 °F). Under these conditions ice may
form in the pilot relay causing diminished or total loss of position
control.

Possible Solutions: Ensure supply gas is clean and dry. Check and

clean the regulator filter.