ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

97


Training Status is present on this page because one or more fields or graphs shows data
that was gathered during the training process. The field shows one of the following states:

Training Enabled - which indicates system data is being recorded. Training should

run during normal system behavior.

Training Disabled - which indicates NO system data is being recorded.

Training Complete which indicates that the time period for training has expired and

the data is stored in the positioner.

NOTE: The Training function requires the Pro positioner upgrade level (522MD+).


Action Buttons
The Apply button will save changes to the connected device.


The Retrieve button will retrieve the latest information from the device.


Warnings and Alarms

Pneumatic Leak

Definition: The positioner has detected a leak in the actuation

assembly.

Implications: Leakage from the actuator can cause decreased

responsiveness and excessive air/gas consumption.

Possible Solutions: Repair pneumatic leaks at the tubing junctions

and actuator seals. Check spool valve for excessive wear.