Flowserve Logix MD+ ValveSight User Manual

Page 37

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

37


Supply Pressure High

Definition: The supply pressure is above the user set warning limit.

Implications: Supply pressure that exceeds the maximum rating on the

actuator can become a potential hazard.

Possible Solutions: Regulate the supply pressure at the positioner

below the maximum limit recommended for your actuator. Recalibrate
pressure sensors. Check the pressure sensor board
connections. Replace pressure sensor board if necessary.

Supply Pressure Low

Definition: The supply pressure is below the user set warning or alarm

limit.

Implications: Low supply pressure can cause poor valve response or

positioner failure. The minimum recommended supply pressure for
proper operation is 1.3 bar (19 PSI).

Possible Solutions: Regulate the supply pressure at the positioner

above 1.3 bar (19 PSI). Ensure system air/gas supply is
adequate. Repair kinked or restricted supply tubing. Check for
pneumatic leaks in the actuator and actuator tubing. Recalibrate
pressure sensors. Check the pressure sensor board connections and
replace pressure sensor board if necessary.

Actuation Ratio

Definition: The force required to control the system is close to the

maximum available force.

Implications: Actuation Ratio is based on the ratio of available force to

the required force to fully actuate. Control may be lost if this ratio
reaches 100%. It is affected by the process load, friction, spring force,
and available supply pressure.

Possible Solutions: Increase the supply pressure. Reduce the

friction. Check the actuator spring. Resize the actuator. Adjust user
set limits.

Spring Fail

Definition: Upon loss of air supply, the valve may not move to the fail-

safe position.

Implications: The spring alone is not adequate to overcome the friction

and process load in the system. The system is relying on pneumatic
force to actuate in the direction the spring is pushing. The failsafe

Advertising
This manual is related to the following products: