Flowserve Logix MD+ ValveSight User Manual

Page 204

Advertising
background image

ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®

FCD-

LGENSF0014-00

© Flowserve Corporation

204


The Command Source field indicates weather the positioner is being controlled by digital or
an analog (4-20 mA) command source.


Information
When performing a new calibration, the positioner will automatic store a new calibration
history, which includes the positioner date and time and the name or initials of the person
performing the calibration. It is recommended to change the “New Calibration by” field to
the name or initials of the person performing the calibration.

Date Last Calibrated field the date and time of the last valid Input calibration.

Last Calibrated By
shows the initials or name of the last person to perform the input
calibration.

Positioner Date and Time
shows the current values from the positioner. To adjust the
positioner date and time, click on the “Configure” link.

Use the New Calibration By field to enter the name or initials of the person performing a
new calibration. This field is limited to 3 characters.


Monitor
Command A/D displays the output of the analog to digital converter on the positioner. This
is the value the positioner will use to determine the input current.

Design Current
shows the internal calculation of the input current. This is for reference
only.